PDS883 Remote-Seal Differential Pressure Transmitter
Features a dual remote-seal system for differential pressure and level measurement in high-temperature, corrosive, viscous, and crystallization-prone media. Designed to reduce impulse line maintenance.
Technical data
| Best measurement accuracy: | ±0.1%FS | Measuring range: Differential: | -0.5 ~ 14 MPa |
| Maximum turndown ratio: | 20:1 | Process temperature: | Standard, KN3.2: -20°C ~ +400°C; standard, KN17: -90°C ~ +120°C; vacuum, HV2: -10°C to +230°C |
| Pressure rating: | Flange pressure rating: ANSI 150 to ANSI 2500; DIN PN10 to PN160 | Communication protocols: | HART 7, PROFIBUS-PA 3.02, FOUNDATION Fieldbus 6.1.1, Ethernet-APL, AutBus |
| Output signal: | 4–20 mA DC with HART; digital fieldbus signals | Power supply: | 4–20 mA: 10.5 to 45 VDC; HART communication: 15.8 to 45 VDC; PA/FF: 9 to 32 VDC; Ethernet-APL: 9.6 to 15 VDC |
| Long-term stability: | ≤±0.1%FS over 10 years | Body temperature effect at 1:1 turndown: | ≤±0.41%FS/28°C |
| Response time: | ≤90 ms | Ambient temperature: | -40°C ~ +85°C |
| Ingress protection: | IP66/IP67 | Damping setting: | 0 ~ 100 s |
| Electrical entries: | M20×1.5; 1/2 NPT | HART loop load: | 230 ~ 500 Ω |
| Power supply effect: | ≤0.005% of calibrated span/V |
Features & Benefits
Dual Remote Seals, Flexible Measurement
A dual remote-seal system designed for level and differential pressure measurement in closed vessels.
Remote Isolation, Versatile Media Handling
Isolates process media from the sensor for compatibility with challenging media.
Reduced Clogging, Easy Maintenance
Avoids conventional impulse piping, reducing clogging and heat tracing maintenance.
Configuration Options, Flexible Installation
A range of flange, diaphragm, and capillary configurations available.
Smart Diagnostics, Easy Configuration
Supports intelligent diagnostics and remote configuration.